Glossary

Term, Abbreviations, AcronymsDescription
2NA redundancy model which ensures that every component has a power backup such that the data center has no single point of failure.
AAmp, a unit of electrical current.
ACSee Alternating Current (AC).
ACAESee Air Conditioning Airflow Efficiency (ACAE).
Access EnrollmentEquinix Customer Portal requires a security access assignment. You can request "grant access" or request "remove access".
Access TokenA credential used to communicate with the API.
ACLSee Access Control List (ACL).
Access Control List (ACL)The list used by customers to enable and communicate site access authorization of approved employees and third-party vendors. Customers can maintain their ACLs via GCP/ECP or by contacting the Equinix Global Service Desk (GSD).
Additional Interconnection ProductsThese additional interconnection services cover cabling services such as Intra Facility Cabling (IFC) and Patch Cable Installations.
AggregatorOn Enterprise Equinix Fabric, aggregators are Network Service Providers (NSPs) and Managed Service Providers (MSPs) who provide multi-tenant services. Aggregators are both buyers of Equinix Fabric service from Equinix and sellers of value-added services over Equinix Fabric to their end customers.
AHUAir Handling Unit
Air Conditioning Airflow Efficiency (ACAE)The amount of heat removed per standard cubic foot of airflow per minute.
Air MixingThe unintended mixing of cold and hot air.
Airside EconomizerA device consisting of fans, ducting and a control which utilizes outside air directly to cool the data center when environmental conditions allow. Air is typically filtered, brought into existing distribution system and then exhausted back to the atmosphere.
AisleThe open space between rows of racks. Best practice dictates racks should be arranged with consistent orientation of front and back to create ‘cold' and ‘hot' aisles.
Alternating Current (AC)The designation given to power that is delivered in the form of a sinusoidal wave form. AC won out over DC as the preferred method of delivering and using power in the industrial age due to the ease of voltage transformation using static devices (transformers).
AMAccount Manager
AMERAmericas (United States, Canada, Brazil)
AMSAsset Management System
APAsia Pacific, also known as APAC
APIApplication Programming Interface
APACAsia Pacific, also known as AP
ARDAlternate Resolution Date
ASHRAEAmerican Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) is an international technical society organized to advance the arts and sciences of air management.
A-sideThe Ordering Customer Point.
A-side DemarcThe Ordering Customer Demarcation Point.
AssetsAll products pertaining to interconnection and colocation installation services. For a full list of assets, refer to List of Assets under the Appendix section.
ASTSAutomatic Static Transfer Switch
Authentication KeyThe Authentication Key is a unique identifier authorizing Equinix to provision a connection towards the CSP. This Key usually contains alphanumeric characters. Note: to Equinix, an Authentication Key is a generic term and is not encrypted on Equinix Fabric. Cloud Service Providers might use a different name to refer to the same key. For example: Azure ExpressRoute calls the authorization key the “service key” while AWS calls it the “account ID.”
Authorization keyThe authorization key typically contains alpha-numeric characters and is a unique identifier authorizing Equinix to provision a connection towards the CSPNote: To Equinix, authorization key is a generic term and is NOT encrypted on Equinix Fabric. CSPs might use a different name to refer to the same key. For example: Azure ExpressRoute calls the authorization key the “service key” while AWS calls it the “account ID”
BACnetA data communication protocol for building automation and control networks.
BASBuilding Automation System
BCIBusiness Contact Information
BCMBranch Circuit Monitoring
BCTRSee Business Continuity Trading Room (BCTR).
BGPBorder Gateway Protocol. A standardized exterior gateway protocol designed to exchange routing and reachability information between autonomous systems on the internet.
BGP SessionA routing session configured between two peers using the BGP. For standards reference, please see http://www.ietf.org/rfc/rfc4271.txt
BICSIBuilding Industry Consulting Service International
Blanking PanelA device mounted in unused U spaces in a rack that restricts recirculation airflow, also called blanking or filler plates.
BMMRSee Building Meet Me Room (BMMR).
BMRBiometric Reader
BMSBuilding Management System, synonymous with BAS, AMS and other computer-based tools used to manage data center assets.
BOMBill of Material
Branch Circuit Monitoring (BCM)A monitoring system used to record and monitor an individual electrical circuit. Typical parameters that are monitored include amperage, voltage, power factor, apparent power (volt-amps), real power (watts) and energy usage (watt-hours). The branch circuit is typically defined to be the circuit fed by a single breaker or 3 phase set of breakers in a multi breaker panel.
Building Meet Me Room (BMMR)A Building Meet Me Room (BMMR) is an MMR within the same building where an Equinix IBX customer can connect with a non-Equinix IBX customer.
For more information, see Extended cross connects in the Cross Connects Data Sheet.
Business Continuity Trading Room (BCTR)A dedicated space that allows customers business recovery and continuity in the event of a crisis.
For more detailed information, see Business Continuity Trading Rooms.
BTUBritish Thermal Unit, a unit of energy. 1kWh = 3412BTU. Cooling equipment capacity is commonly specified in BTU/hr.
BuyerA buyer is a user who connects to an available service through Equinix Fabric. A buyer can be an enterprise end customer of the seller service or an aggregator, managed service provider, network service provider or system integrator company that bundles its service offerings with Equinix Fabric.
BYOLBring Your Own License (BYOL) means that you’ve already procured a license from the vendor and will enter it into the NE portal to activate the device. There are no charges associated with this license type since your licensing arrangement is directly with the vendor.
Bypass AirflowConditioned air that does not reach computer equipment. With fixed speed fans (common in DX equipment), some bypass air is inevitable and without containment, some bypass air is prudent. Unintended bypass air can occur by escaping through cable cut-outs, holes under cabinets, misplaced perforated tiles or holes in the computer room perimeter walls.
CDegrees Celsius
C/HCooling/Heating
CABSee Cabinet (CAB).
Cabinet (CAB)A closed structure inside our data centers that houses servers typically made of metal with rails, grounding studs, interior shelving, etc. Cabinets house the customer's equipment within a private cage.
For more information on Equinix cabinets, see Cages and Cabinets.
CACSee Cold Aisle Containment (CAC).
CADECorporate Average Data Center Efficiency.
CageA cage is a secluded, secure area within a data center where customers install cabinets and power circuits. The enclosure subdivides colocation space within a data center using mesh walls, a door, security panels, etc.
For more information on Equinix cabinets, see Cages and Cabinets.
CapExCapital Expense, the cost of purchasing capital equipment.
Campus Cross ConnectA cross connect type that allows the customer to connect to a service provider in a different IBX no further than 10km away using single-mode fiber. Campus cross connects are a subset of standard cross connects.
For more information, see Cross Connects Data Sheet.
Carbon FootprintA measurement of the volume of Carbon Dioxide generated by business operations, units are commonly metric tons.
Carbon Usage Effectiveness (CUE)A metric defined by the Green Grid, which is a measure of data center sustainability in terms of data center specific carbon emissions. CUE is calculated by dividing the “total CO2 emissions caused by total data center energy” by the “energy consumption of the IT computing equipment”. An alternative way to calculate CUE is by multiplying the data center’s annual PUE by the Carbon Emissions Factor for the region as determined by the EPA. The units of CUE are kilograms of carbon dioxide per kilowatt-hour.
CCSee Cross Connect (CC).
CFACarrier Facilities Assignment or Circuit Facility Assignment
CFDComputational Fluid Dynamics, a numerical analysis technique commonly used in the analysis of airflow in data centers.
CFMCubic Feet per Minute, a unit of flow rate, commonly used to specify airflow.
CFRCapacity Feasibility Review
ChillerA unit consisting of a compressor, a condensing section and an expansion section. The condensing and expansion sections nearly always have water or glycol as the heat transfer agent to the rest of the system; primary water/glycol on the condensing side and secondary water on the expansion side.
Close Coupled CoolingCooling technology that is installed adjacent to server racks, minimizing the path that air must flow from the cooling unit through the IT equipment and back to the cooling unit.
Equinix Fabric PortA type of network port that connects customer to leading cloud service providers (CSP) on the Equinix Fabric™.
CMRCritical Maintenance Request
COChange Order
CoESee Coefficient of Effectiveness (COE).
Coefficient of Effectiveness (COE)Uptime Institute metric based on the Nash-Sutcliffe model efficiency coefficient.
Coefficient of Performance (COP)Used to rate the effectiveness of heat pumps or cooling units. It is the ratio of the load on a cooling unit and the energy that it uses.
Cold AisleAn aisle where rack fronts face into the aisle that cool air is directed to.
Cold Aisle Containment (CAC)A system that directs cool air from air conditioning equipment to the inlet side of racks in a highly efficient manner.
Cold SpotAn area where ambient air temperature is below desired levels. Typically caused by ineffective airflow management necessitating a temperature setpoint lower than that which would be required with proper airflow management.
ColoSee Colocation (Colo).
Colocation (Colo)A practice in which many different companies or "tenants" share a data center building for economic efficiencies, as well as to digitally interconnect with other companies within the same facility or campus.
Component/microserviceA piece of an overall solution that can be built individually or as part of a larger end-to-end solution
Computer Room Air Conditioner (CRAC)CRAC (pronounced crack) uses refrigerant and a compressor. Cooling of the air in the data center is accomplished by airflow over the evaporation coils where the refrigerant is being "directly expanded" (see DX).
ComputeCompute refers to the resources or assets necessary to run a device in the ENE platform. In most ways, the ENE platform is an infrastructure as a service platform underneath, but we typically do not ask customers to get involved in that aspect of the platform. To run efficiently, each device and/or service requires some pre-determined amount of compute. Equinix has thoroughly tested each device and service with the vendor before offering it to the public. This testing ensures that the amount of compute selected on the user's behalf is already optimized to run smoothly with the vendor's recommendations. Customers do not need to customize or tweak the compute in most cases.
ConnectionConnection is a general term that refers to any solution that results in the ability to pass data from one point to another. Connections can be made with Layer 2 or Layer 3 technology, may involve several parts or components and can be created from the portal or with APIs in a variety of ways.
ContainmentUsing either long curtains or rigid plastic to maintain a physical barrier between a hot and cold aisle. Keeping warm exhaust air away from the intake of the server racks is a crucial part of making any data center more efficient.
Cooling TowerA device which cools water via the direct evaporation of some of the water. Water is pumped into the top of the cooling tower and allowed to run down over the fill, typically pads or strips into a sump at the bottom of the cooling tower. Air is drawn in from the sides over the fill by fans in the top of the tower, evaporating some of the water which cools the remaining water. The temperature of the water in the sump is controlled by varying the speed of the fans. The water in the sump is then used to cool the condensing section of a chiller or to cool the secondary loop directly via a heat exchanger (see water side economizer).
COPSee Coefficient of Performance (COP).
CRComputer Room
CRACSee Computer Room Air Conditioner (CRAC).
CRAHComputer Room Air Handler (pronounced craw) which uses chilled water passing through a heat exchanger to cool air flowing over the heat exchanger.
CRDCustomer Requirements Document
Critical LoadComputer equipment whose uptime is critical, typically supported by a UPS.
CRMCustomer Relations Manager
Cross Connect (CC)A cross connect is a point-to-point cable link between two customers in the same IBX. With cross connects customers receive a fast, convenient and affordable integration with business partners and service providers within the Equinix digital ecosystem. They also get highly reliable, extremely low-latency communication, system integration and data exchange
For more information on cross connects, see Equinix Cross Connects.
CSICold Supply Infiltration index, quantifies the amount of hot air mixing with cold inlet air prior to entering the rack.
CSMCustomer Success Manager (formerly known as client services manager)
Cloud Service Provider CSPA Cloud Service Provider (CSP) is a company that offers some type of cloud services to other businesses or individuals. In this context, that can include: cloud computing, cloud storage, cloud content delivery network (CDN) and more. Typical CSPs include Infrastructure as a Service (IaaS), Software as a Service (SaaS) and Platform as a Service (PaaS).
CTSee Current Transformer (CT).
CUESee Carbon Usage Effectiveness (CUE).
Current Transformer (CT)A device used to transform electrical current from one level to another with a specific ratio. For example, a 5000:5 current transformer transforms current on the primary side to current on the secondary side with a ratio of 1000:1. CTs are typically used to transform large currents to much smaller currents so that standard metering equipment can be used on a variety of circuits by measuring the secondary current rather than the large primary current.
Customer OrganizationA customer grouping within the portal that is comprised of its company accounts.
Customer SignatureCustomer signature required for approval prior to any order fulfillment. This is for customers who specifically request this process step.
CutoutAn open area.
CWChilled Water
CXCustomer Experience
Data Center infrastructure Efficiency (DCiE)A metric developed by the Green Grid, data center infrastructure efficiency is an efficiency measure that is calculated by dividing the IT equipment power consumption by the power consumption of the entire data center. This measure is the inverse of PUE.
D/HDehumidifying/Humidifying.
DCData center
DCSee Direct Current (DC).
DCiESee Data Center infrastructure Efficiency (DCiE).
DCIMData Center Infrastructure Management
Dead BandA control technique which prevents oscillation or unnecessary cycling of a controlled variable. In data center cooling, it typically applies to the action of the CRAC or CRAH relative to the set point. A certain amount of dead band around the set point prevents unnecessary cycling of the compressor or chilled water valve.
Delta TThe difference in temperature across a device. Examples include the temperature difference between the inlet and outlet of piece of IT equipment or between the inlet and outlet of a cooling unit (CRAC or CRAH). Delta T, airflow and thermal dissipation are related: thermal dissipation = airflow x delta T x specific heat of air.
DemarcSee Demarc Point (Demarc).
Demarc Point (Demarc)A demarc (abbreviation for demarcation point) marks the point of the cage/ rack/ panel/ ports where Equinix hands off a cross connect to the customer.
Dew pointThe temperature at which air reaches water vapor saturation. Dew point is constant for a specific amount of water in a specific amount of air while relative humidity varies with temperature. The latest ASHRAE spec for data center environmental conditions includes an upper limit for humidity based on dew point.
Direct Current (DC)A non-time varying method of delivering power. While slightly more efficient then AC if utilized between the DC portion of the UPS and the power supplies in IT equipment, it has not won wide acceptance in modern data centers.
Direct Expansion (DX)The use of refrigerant directly expanded into evaporation coils in the supply air stream of an air conditioning unit.
DiversityTwo physical paths/ ports are created to provide redundancy. When the working path/port is down, the protection path/ port can be used.
Dry CoolerA liquid to air heat exchanger that is a radiator over which air is blown via fans. Typically used as the heat rejection device for water or glycol cooled condensers, may also be used as the heat rejection device for liquid cooled coils in an AHU under proper environmental conditions.
Dry-Bulb TemperatureThe temperature of the air measured using a dry bulb thermometer such that evaporative cooling has no effect. Typically taken in conjunction with a wet bulb reading which does include the evaporative cooling effect in order to determine relative humidity.
Dual-Diverse Metro ConnectA metro connect that provides resiliency for WAN connections with two diverse fiber paths and two switches at each IBX location. This provides further redundancy.
For more information, see Equinix Metro Connect Services.
DWDMDense Wavelength Division Multiplexing
DXSee Direct Expansion (DX).
ECEEEquinix Carrier Ethernet Exchange™
ECOEquinix Customer One. A company-wide platform to simplify and standardize the way we do business with our customers.
EconomizationA way of utilizing the local environment around the data center to aid in cooling of the IT load by natural means rather than use more energy. There are two common types of economization: Airside Economization, and Waterside Economization; sometimes referred to as LINK. Economization is a great benefit to those who can take advantage of it due to the large energy-saving opportunity.
ECPSee Equinix Customer Portal (ECP).
ECX FabricECX Fabric is an advanced interconnection solution that improves performance by providing a direct, private network connection.
EDEquinix Direct
EFCSee Equivalent Full Cabinets (EFC).
EISEnterprise Information Systems
EMEAEurope, Middle East, Africa
End customer/end device/CPEThe entity and/or devices managed by that entity that ultimately interact with the services bought over the ECX platform
ENE"Equinix Network Edge" is a generic industry term referring to the act of turning network actvities, protocols, traffic flow, and design - into a software service or code. This take a lot of forms from purely new network and traffic flow methods and operating systems to making an entire hardware device accessible via a GUI. In Equinix' context we use it loosely to refer to designing and configuring network solutions using our platform and software, regardless of the device, object, component, or vendor
EOCEquinix Operations Center
EQIXEquinix
Equinix ConnectA cross connect from the customer's server to the Equinix connect server in a data center that offers direct access to the public internet.
Equinix Customer Portal (ECP)A self-service portal that allows customers to manage day-to-day interactions including routine requests, opening work tickets, placing orders, and scheduling visits online. Also referred to Global Customer Portal.
Equivalent Full Cabinets (EFC)The number of full cabinets that would exist if all the equipment in the data center were concentrated in full cabinets.
Equinix Infrastructure Services (EIS)Services delivered by Equinix hardware experts for cage design, installation, and structured cabling for new data center deployments.
Equinix Internet ExchangePeering or data exchange between two public internet networks. Equinix Internet Exchange enables customers to exchange internet traffic through public peering on the largest peering platform in the world.
For more information, see Equinix Internet Exchange.
Equinix Professional ServicesServices delivered by our experts for assessing, designing, migrating and optimizing data center and cloud architectures
ESDElectrostatic Discharge, more commonly ‘static discharge'.
ESDEquinix Service Desk, now known as Global Service Desk (GSD).
Extended Cross ConnectA type of cross connect that allows a customer to connect to another customer that is not in an Equinix IBX, but both have a point of presence in the same building, through a Building Meet Me Room (BMMR).
For more information, see Cross Connects Data Sheet.
Extended Fiber ConnectA type of cross connect that links a customer’s cabinet in an Equinix IBX to a third-party Meet Me Room (MMR) in the same metro.
For more information, see Fiber Connect.
Equinix Network EdgeEquinix Network Edge is the latest offer in our interconnection portfolio and represents a significant leap in a customer's ability to deploy and manage network in a rapid on-demand way.
FDegrees Fahrenheit
FGFunctional Group
Fiber ConnectA type of interconnection that allows a customer to link a customer’s cabinet in an IBX to another cabinet in a different IBX in the same metro when a standard cross connect is not available. There are two kinds of Fiber connect: a Fiber Connect, and an Extended Fiber Connect.
For more information, see Fiber Connect.
FOCFirm Order Commitment
fSnDFormer Switch and Data
Ft2Square feet, a unit of area.
GAMGlobal Account Manager
GCCGlobal Customer Care
GCPGlobal Customer Portal. Also referred to as Equinix Customer Portal (ECP).
Global Interconnection Index (GXI)The Global Interconnection Index is an annual report created by our company that tracks, measures and forecasts the growth of Interconnection bandwidth. It allows our customers to see how Interconnection is being built, deployed and consumed around the world. This knowledge helps them better understand how Interconnection can play an important role in their business.
GPLGlobal Process Library
GPMGallons Per Minute, a unit of flow rate.
GPOGlobal Process Organization
Green energyEquinix's commitment to minimizing our environmental footprint through 100% clean and renewable energy which will result in carbon-neutral data centers.
GSDGlobal Service Desk, formerly known as Equinix Service Desk (ESD).
GTSGlobal Technology Services (also referred to as IT)
GXISee Global Interconnection Index (GXI).
HACSee Hot Aisle Containment (HAC).
Harmonic DistortionDistortion in the line voltage waveform. Any cyclical waveform can be described as the sum of sine waves of various magnitudes which are integer multiples of the root frequency (60 Hz, 120 Hz, 180 Hz, etc.). Harmonics are often the result of the nonlinear loading of the power distribution system due to the nature of solid-state power supplies. Harmonics are detrimental to the efficiency and capacity of power delivery equipment and rotating equipment due to increased eddy current losses and non-fundamental frequency torques.
HDGHot Dipped Galvanized.
Heat ExchangerA device used to transfer heat energy from one medium to another. Common uses of heat exchangers are water to air heat exchangers in air handling units, plate and frame heat exchangers in economizers, etc.
Hot AisleAn aisle where rack backs face into the aisle. Heated exhaust air from the equipment in the racks enters this aisle and is then directed to the CRAC return vents.
Hot Aisle Containment (HAC)A system that directs heated air from the outlet side of racks to air conditioning equipment return ducts in a highly efficient manner.
Hot SpotAn area, typically related to a rack or set of racks, where ambient air temperature is above acceptable levels. Typically caused by poor airflow management (insufficient cool air supply or an excess of recirculation).
HpHorsepower
HPDHigh Power Density
HPDCHigh-Performance Data Center, a data center with above average kW loading, typically greater than 10kW/rack.
HrHour
HVACHeating, Ventilation and Air Conditioning system, the set of components used to condition interior air including heating and cooling equipment as well as ducting and related airflow devices.
Hybrid cloudA hybrid cloud is a blended cloud architecture in which private clouds are connected to public clouds, usually for purposes of scaling up and/or delivering data. Hybrid cloud combines the best of public and private clouds.
IBInstalled Base
IBCCIntra-Building Cross Connect
IBIDIntra-Building Inner duct
IBXEquinix International Business Exchange™ (IBX®) data center
IBX AdministratorThe secondary administrator of the customer organization who manages users for selected IBX locations as designated by the Master Administrator.
Equinix Flex SpaceEquinix Flex Space space allows customers to deploy mission-critical operations, equipment and personnel in non-cage space within–or in close proximity to–our IBX data centers.
Equinix Smart ViewEquinix's data center infrastructure monitoring product which gives our customers online, on-demand access to highly relevant environmental and electrical information about their Equinix deployments. The solution provides real-time visibility into core operating data relevant to a customer's data center footprint such as temperature, humidity, and power draw data for a specific cage.
ICEInternet Core Exchange
IDFIntermediate Distribution Frame
IEEEInstitute of Electrical and Electronics Engineers
IFCSee Intra Facility Cable (IFC).
IMImplementation Manager
Inlet AirThe air entering the referenced equipment. For air conditioning equipment this is the heated air returning to be cooled, also called return air. For racks and servers this is the cooled air entering the equipment.
In-Row CoolingCooling technology installed between racks in a row that draws warm air from the hot aisle and delivers cool air to the cold aisle, minimizing the path of the air (see close coupled cooling).
InterconnectionDirect, private connections between two parties which enables the ability to exchange data without need for an intermediary.
Interconnection BandwidthThe total capacity provisioned to privately and directly exchange traffic with a diverse set of counterparties and providers at distributed IT exchange points.
Interconnection ProductsProducts that facilitate physical connections within or between IBX locations, or virtual connections to service providers.
For more information, see Interconnection Products.
InterfaceAn interface is a point on a device where data flows in and out. The virtual device is like a physical device because it has some amount of interfaces that allow it to transmit and receive data from the outside world. This can be in the form of an Internet connection, a connection to ECX, a service chain to another virtual device or any other communication.
Internet exchangeSee Equinix Internet Exchange.
Internet Exchange PortA type of network port that starts peering on the Equinix Internet Exchange.
Intra-Customer Cross ConnectA cross connect type that allows a customer to connect to their own cage or cabinet in the same suite or floor of the same IBX.
For more information, see Cross Connects Data Sheet.
Intra-Facility Cabling (IFC)An Intra-Facility Cabling (IFC) connects colocation spaces to the Meet Point Room for interconnection via Cross Connect.
Intra-Facility Cross ConnectA cross connect type that allows a customer to connect to another customer in select IBX locations where a Meet Me Room (MMR) architecture is used.
For more information, see Cross Connects Data Sheet.
IPInternet Protocol, a communications technology using the internet for communications.
IPv4Version 4 of the IP protocol providing 32-bit addresses. For standards reference, please see http://www.ietf.org/ rfc/rfc791.txt
IPv6Version 6 of the IP protocol providing 128-bit addresses. For standards reference, please see http://www.ietf.org/ rfc/rfc2460.txt
IP TransitRefers to Internet Access.
IRIncident Report
IRInfrared spectrum used by thermal imaging technologies.
IXPInternet Exchange Point
IX PlatformA network platform enabling the exchange of IP traffic between multiple peers on a many-to-many basis
IX PointA specific instance of an IX Platform
JVMJava Virtual Machine, Java interpreter. Software that converts the Java intermediate language into executable machine language.
kBTUKilo British Thermal Unit, one thousand BTU (see BTU).
kCFMKilo Cubic Feet per Minute, one thousand CFM (see CFM).
kVKilovolt, one thousand volts, (see V).
kVAKilovolt Amperes = voltage x current (amperage) (see VA)
KVMKeyboard, Video, Mouse, an interface technology that enables users to access multiple servers remotely from one or more KVM sites. More obscurely, can also mean Kernel base Virtual Machine: a version of the Java Virtual Machine for small devices with limited memory.
kWKilowatt
kWhKilowatt-hour, one thousand watt-hours (see Wh). kWh is a common unit of electrical energy.
Latent CoolingThe process of condensing water out of air, then evaporating the water later. Energy is given up by the water during condensation. If the water is then later evaporated (such as from a drip tray), the amount of energy used to evaporate the water is the same as the amount of energy given up by the water vapor to the cooling equipment when it was condensed. Cooling is occurring later in time, hence the name "latent cooling". In a system where condensed water is pumped or drained away, the cooling that may occur from evaporation does not cool the environment where the condensation took place, so the cooling capacity spent condensing the water vapor is wasted energy.
Latent Cooling CapacityCooling capacity related to wet bulb temperature and objects that produce condensation.
Layer 2 (switching)When the ECX Fabric makes forwarding decisions at the Ethernet protocol level (Layer 2), and does not examine the IP addressing the service
Layer 3 (routing)Layer 3 connections occur when the ECX Fabric makes customer traffic forwarding decisions by examining the IP addressing of that traffic.
LECLocal Exchange Carrier
LicenseMost virtual devices require a license from the vendor to deploy and operate the device. It will come with certain settings, such as maximum throughput and speeds, operating system, and other parameters. Individual vendors may have specific license types or terms, and users are encouraged to consult the vendor documentation to learn more about the options available.
Line NoiseDistortions superimposed on the power waveform that may cause electromagnetic interference.
Liquid CoolingA general term used to refer to cooling technology that uses a liquid evacuate heat. In data centers, the two prevalent forms of heat evacuation are liquid (chilled water) and refrigerant (DX).
LOALetter of Authorization
LoadThe demand placed on a system, typically used to describe the electrical demand on the electrical supply system or the cooling demand on the cooling system. Units are power such as kW, BTU/hr., Tons, etc.
MACDMove, Add, Change, Delete
MAHMakeup Air Handler, an air handler that conditions and delivers outside air into an occupied space.
Make-Up AirThe conditioned air delivered by a MAU or MAH.
Managed servicesServices offering proactive monitoring of a customer's equipment.
Master AdministratorThe primary administrator of the customer organization who manages all administrators and users access and permissions for all accounts across all locations within a portal organization.
MAUMakeup Air Unit, synonymous with MAH.
Maximum Temperature Rate of ChangeAn ASHRAE standard established to ensure stable air temperatures. The standard is 9 degrees F per hour.
MCSee Media Converter (MC).
MDFMain Distribution Frame
Media Converter (MC)A media converter (MC)connects two dissimilar media types. e.g. fiber optic cabling can be connected to copper-based cabling with an MC.
Meet Me Room (MMR)A space within a data center where ISPs, telecommunications carriers, cable companies and other companies handling lots of digital traffic can connect to one another and exchange data.
In the case of Equinix, an MMR facilitates connections exclusively between Equinix customers.
Only select IBX locations within the Americas and the EMEA region use MMR architecture.
For more information, see Intra-facility cross connects in the Cross Connects Data Sheet.
MERVMinimum Efficiency Reporting Value, ASHRAE 52.2, for air filtration measured in particulate size
Metro ConnectA point-to-point link between two IBX locations in the same Equinix metro area.
Equinix Metro Connect services provide direct, dedicated, carrier-grade network links between customers in one IBX data center and partners in another IBX within the same metro. With Metro Connect, customers enjoy fast, convenient and affordable integration with customers, partners and service providers within the Equinix digital ecosystem. Customers' organizations benefit from highly reliable, extremely low-latency communication, system integration and data exchange
For more information, see Equinix Metro Connect.
MLPEMulti-Lateral Peering Exchange
MMFMulti-Mode Fiber
MMRSee Meet Me Room (MMR).
Mobility ExchangeA fully managed, Ethernet-based switching platform designed specifically for exchange of mobile internet traffic.
GPRS (General Packet Radio Service) roaming exchange. A platform allowing the exchange of roaming traffic between mobile network providers
For more information, see Equinix Internet Exchange.
Mobility Exchange LocationAn Equinix IBX location or campus with a Mobility Exchange present
MPOEMinimum Point of Entry
MRCMonthly Recurring Charge
MRRMonthly Recurring Revenue (Interpretation of MRC for internal use)
Managed Service Provider (MSP)A Managed Service Provider (MSP) is a business entity that helps enterprises architect, build and support a technology strategy that may include ECX. Often also called system integrators, consultants or others. An MSP may frequently aggregate customers similar to an Network Service Provider (NSP).
Multi-homedIt refers to Dual Port configuration.
N+1Need plus one, a redundancy concept where capacity is configured to include used capacity plus one additional device to enable continued operations with the failure of one system in the configuration.
NEBSNetwork Equipment-Building System design guidelines applied to telecommunications equipment.
Network PortsNetwork ports are physical ports that facilitate network connectivity. This includes Internet Exchange Ports, Equinix Fabric Ports, and ports for Metro Connect.
NFVNetwork Functions Virtualization is the result of turning network activities, protocols, traffic flow and design into a software service or code. NFV takes a lot of forms from purely new network and traffic flow methods and operating systems to making an entire hardware device accessible via a GUI. At Equinix, we use the term to refer to designing and configuring network solutions using our platform and software, regardless of the device, object, component or vendor. Network Edge is the first NFV offer in our interconnection portfolio and represents a significant leap in a customer's ability to deploy and manage network in a rapid, on-demand way.
NNINetwork to Network Interface
No.Number
NOCNetwork Operations Center
Nominal Cooling CapacityThe total cooling capacity of air conditioning equipment includes both latent cooling and sensible cooling capacities.
Non-Streamlined customerA Non-Streamlined customer is a customer who must approve the pricing of every individual order in the portal before it can proceed for fulfillment. After creating an order, the portal will prompt the approving user with a message for Orders on Hold. This user must either accept or reject the one-time and monthly fee(s) presented to them in order for the order status to change from 'Pending Action Required' to 'Submitted' or 'Cancelled'.
NPA/NXXArea Code and First 3 Digits of a Phone Number
NRCNon-Recurring Charge
NSENetwork Support Engineering
Network Service Provider (NSP)A Network Service Provider (NSP) is a business entity that provides and sells services such as network access (local loop, wide area network (WAN), Internet transit) and bandwidth. NSPs are also referred to as carriers
NTPNetwork Time Protocol
OAuthOAuth (Open Authorization) is an open standard for token-based authentication and authorization on the Internet.
OMOrder Management
OpExOperating Expense, the ongoing expenses related to operating the data center.
Optional Service Network ServiceOptional service and network service refer to a series of independent features that can be added to a component, connection, device or other object. Example services might be SSH or Network Address Translation. The service is usually defined with one or more fields to configure and prepare it for launch into production, and may have restrictions on when it can be added or deleted. Although most are optional, you may find that some complete solutions or offers will not operate properly without a specific service or series of services. Some services will also have additional associated charges.
Order Status TypesOrders are tracked from submission to completion, and users would be updated of the order status as it is changes. Order status types are as follows: In Quote, Order Received, In Progress, On Hold, Pending Action Required, Completed, and Cancelled.
OvercoolingA situation where air is cooled below optimum levels. Typically used in reference to rack inlet temperatures.
Patch Cable InstallationInstallation of a cross connect patch cable.
PDUSee Power Distribution Unit (PDU).
Power Distribution Unit (PDU)This typically refers to one of two pieces of equipment in the power delivery chain. One is the combination transformer/breaker panel that is often used between a UPS supplying voltage higher than that used by the IT equipment and the cabinets. The other is the smaller "power strip" like device that is used inside the rack to distribute power to the IT equipment.
PeeringA voluntary interconnection between separate Internet networks to directly exchange data. This is typically a settlement-free business relationship whereby companies reciprocally provide access to each other’s customers at no additional cost.
PermissionsPermission is the access granted to a user via the portal through the authority of the Master Administrators. The Master Administrator would grant the user access and permissions to customer portal products and services. Depending on the permissions granted to the user, they would be able to make orders, submit trouble tickets, generate reports, etc. for select IBX. Without permissions from the Master Administrator, the user would not have access to the portal.
PFSee Power Factor (PF).
PHSee Phase (PH).
Phase (PH)Phase (PH) is a term that describes the relationship between multiple time varying waveforms which have a constant frequency but differ in their position relative to time. It is also used to refer to the number of sinusoidal voltages that make up the power delivery to a device. Most common are three phase and single phase. Single phase consists of 2 conductors between which a sinusoidal voltage is present. Three-phase is a set of 3 or 4 conductors. In the case of 3 conductors, a sinusoidal voltage of a constant magnitude and frequency but differing relationship with respect to time exists between any 2 conductors. In a 4 wire system, the same voltage as in the 3 wire case exists between any of the three "hot" conductors and in addition, between any of the three "hot" conductors and fourth neutral conductor there exists a voltage that is smaller by a factor of the square root of three than the voltage between any of the "hot" conductors. An example of this is a 208/120 three phase system. 208 volts exists between any of the three "hot” conductors and 120 volts exists between any of the "hot" conductors and the neutral conductor.
PII holdPII (Post Initial Install) hold is an ordering hold automatically applied to customers that are Non-Streamlined, or customers that requested a final approval process prior to final submission of orders. Customers must provide final approval within 10 days of order , failing which the order will be automatically cancelled.
Plate and FrameA type of heat exchanger commonly used in water to water systems. It is a series of plates held in a frame through which exist 2 paths for water which are adjacent but separate. Plate and frame heat exchanges are simple to size via the addition of additional components and maintenance is straight forward via disassembly.
PlenumA receiving chamber for air used to direct air flow.
PMProject Manager
PMOProject Management Office
PNIPrivate Network Interface
POPurchase Order (PO) is a blanket purchase order by the customer. This PO number would be validated and tracked when customer creates an order or submits a trouble ticket in the portal.
POCPoint of Contact (see SPOC)
PoleA row of power receptacles with power supplied from a PDU.
Pole PositionA power receptacle on a pole.
Potential Transformer (PT)A device used to transform electrical potential (voltage) from one level to another with a specific ratio. For example, a 480:120 potential transformer transforms voltage on the primary side to voltage on the secondary side with a ratio of 4:1. CTs are typically used to transform large voltages to much smaller voltages so that standard metering equipment can be used on a variety of circuits by measuring the secondary voltage rather than the large primary voltage.
POTSPlain Old Telephone Service
POWPower Item
Power Factor (PF)Powere Factor (PF) represents the portion of the apparent power that is real power. The source of power factor is non-resistive components (inductors and capacitors) in the load on an AC power system. These components draw current that is 90 degrees out of phase with the voltage across them resulting in zero real power being delivered. While the power delivery system must carry this current (as well as all the current which does result in real power being delivered), it does no useful work. Power companies often charge a penalty for loads which have a power factor that is significantly far away from 1.0 since the size of the equipment that must be in place is dependent upon the total current delivered, but normal billing is based on real power delivered.
PPPPolicies, Procedures, Processes
Pressure DifferentialThe difference in pressure between two locations in the data center. Air flows from higher pressure areas to lower pressure areas. Often, the pressure differential between the underfloor plenum and the above floor space is controlled by varying the speed of the fans supplying air to the underfloor plenum. This allows the addition of vented floor tiles to occur without affecting the air delivered to existing vented floor tiles so that additional IT load may be placed on the floor without disturbing the tuning of the existing floor.
PricingThe one-time and recurring fees presented to the non-streamline customer user for approval to process an order for fulfillment. Until the pricing approval is carried out by the user, the status of the order will remain as 'Pending Action Required'.
Primary LoopRefers to the water loop which cools the condenser side of a chiller. This loop is cooled by dry coolers or cooling towers.
Private Patch PanelA dedicated patch panel in the Meet Me Room (MMR) to reduce lead time and/or lower costs for customers.
For more information, see Intra-facility cross connects in the Cross Connects Data Sheet.
Protected Metro ConnectA metro connect that provides resiliency for WAN connections with two diverse fiber paths using a single switch at each IBX.
For more information, see Equinix Metro Connect Services.
PTSee Potential Transformer (PT).
PUPackaged Unit, an air handler that is a complete device shipped ready for use rather than a custom device that is assembled on site from components.
QOHQuantity on Hand
RackRefer to Cabinet (CAB).
RAHRecirculation Air Handler, a device that circulates air but does not cool the air.
Raised FloorMetal flooring on stanchions that creates a plenum for airflow and cabling, synonymous with RMF.
Rate limitA rate limit is a bandwidth control that is placed on a connection or service that limits the amount of traffic that can be sent or received to an amount less than the physical size of the ports. This is also referred to as a policer or “policing” a service, and is typically implemented using a VLAN on a sub-interface.
RecirculationAir which exits IT equipment and then re-enters either the same IT equipment or another piece of IT equipment without being cooled. Typically caused by poor control of airflow due to missing blanking panels, gaps in rows, insufficient air supply, etc.
Refresh TokenA token that contains the information required to obtain a new Access Token.
ReportsConsolidated records for customer reference. Various reports can be generated on a regular or ad-hoc basis in the portal and downloaded in Excel format. These include reports for assets, security, finance, as well as for site and environment.
Return AirThe heated air returning to air conditioning equipment.
RFIRadio Frequency Interference.
RhRelative Humidity.
RMFRaised Metal Floor, an alternate term for the more commonly used term 'raised floor'.
ROIReturn on Investment, a measure of the money that an entity earns as a percentage of the total value of its assets that are invested.
RPMRevolutions per Minute, a unit of angular velocity.
RPPRemote Power Panel
RTURooftop Unit, an air handler designed for outdoor use mounted on a rooftop.
S+SSystem plus system.
SCFMStandard Cubic Feet per Minute, the volumetric flow rate of a gas corrected to standardized conditions of temperature, pressure and relative humidity.
SDNSoftware-Defined Networking (SDN) is another industry term sometimes interchangeable with NFV but SDN often refers to a more specific set of protocols and rules about the flow of traffic and data. SDN frequently means the separation of the flow of the data from the control and management of the network in the form of software.
SESales Engineer
Secondary LoopRefers to the water which is used to cool the heat exchangers in AHUs and is cooled via the expansion unit in a chiller.
SellerA seller is a user who makes their services available to end customers through ECX. This guide refers to sellers for shorthand, but ECX generally regards a “seller” as an activity rather than a static person.
sFlowA method of collecting network traffic statistics from network hardware. Used to compute the inbound and outbound traffic statistics on the IX Portal. For standards reference, see http://www.ietf.org/rfc/rfc3176.txt
Sensible CoolingThe action of lowering the dry bulb temperature of air without condensation taking place.
Set PointIn a control system, this is the value against which the variable that is being controlled is compared. Temperature and humidity set points are common in the cooling system for a data center.
SHSmart Hands
Short CyclingChilled airflow returning to cooling units without passing through IT equipment, also referred to as bypass.
Single-homedIt refers to Single Port configuration.
SLAService Level Agreement.
SLOService Level Objective
Smart HandsSmart Hands is an around-the-clock, on-site, operational support service for remote management, installation and troubleshooting of your data center equipment.
For more information, see Smart Hands.
SMESubject matter expert
SMFSingle Mode Fiber
SOPStandard Operating Procedure
SOWStatement of Work
SPOCSingle Point of Contact (see POC)
SRService Request
SSHSecure Shell is a protocol that allows customers to connect to a device (that supports and has enabled SSH) directly. This allows the user to access all features of the device, including those not supported from the portal or API, and make changes, manage and observe and other activities. Caution: if a user connects into a device directly and makes changes that are not tracked or possible from the portal or API, some functions may fall out of sync and may into work at all and Equinix cannot guarantee support and accuracy once this occurs.
Standard Cross ConnectA cross connect type that allows the customer to connect to a service provider in the same IBX or a different IBX within an Equinix campus.
For more information, see Cross Connects Data Sheet.
STORflexStorage Space
Streamlined customersA Streamlined customer is a customer that can place orders and submit tickets for immediate fulfillment. They do not have to go through an additional pricing approval process that Non-Streamlined customers must do in order to proceed with their orders.
STSStatic Transfer Switch, a solid-state device which transfers the feed of power from one source to another source such as from the incoming utility to a generator.
Sub-FloorThe open area underneath a raised computer floor, also called a sub-floor plenum.
Subscription LicenseSubscription license is provided by Equinix on an ongoing basis and is billed by the month. While not a pure "pay as you go" model, this is the typical license you would select if you do not already have one from the vendor or as part of a larger contract that your company has. There will be monthly charges on your invoice associated with this license.
SuiteA secured, custom built (as per customer’s requirement) area fully enclosed by solid partitions to house multiple cabinets in it. Suites may be private (housing only one customer), or shared (housing multiple customers).
Supply AirThe cooled airflow emitted from air conditioning equipment.
TCETriton Coefficient of Effectiveness, a data center efficiency metric developed by the Uptime Institute synonymous with UCE. (See also CoE)
TCYTelecity
ThermistorA type of resistor with resistance varying according to its temperature.
TIATelecommunications Industry Association
Trouble ticketAn order that a user submits through the Equinix Customer Portal to resolve an IBX issue that is impacting their service. A trouble ticket must be submitted for any IBX issues pertaining to the following:  power; cross connect; environment; hardware; network; security; smartview.
For more information, see Trouble Ticket in the Equinix Smart Hands™ Welcome Guide.
TSATransition Services Agreement
UA unit of space in a rack, equal to 1.75". The vertical dimension of racks and IT equipment is often specified in "Us" such as 42U.
UCEUpsite Coefficient of Effectiveness, a data center efficiency metric developed by the Uptime Institute synonymous with UCE. (See also CoE)
Uninterruptible Power Supply (UPS)A device placed in series with the supply of power from the utility which contains energy storage such that the supply of power from the UPS is continuous even when the utility supply is removed. While battery-based energy storage is the most common, flywheel-based energy storage is gaining in popularity due to the reduced maintenance cost.
Unprotected Metro ConnectA metro connect that provides Inter-IBX connectivity within a metro over a single fiber path. This offering does not provide any redundancy.
For more information, see Equinix Metro Connect Services.
UPSSee Uninterruptible Power Supply (UPS).
UserA user of the customer organization who can place orders in the Equinix Customer Portal in accordance with the permissions granted to them by the Master administrator and IBX administrator.
VVolt, a unit of electrical potential.
VAVolt-Ampere, a unit of apparent power. In AC circuits, the magnitude of the voltage across a circuit times the current through the circuit is the apparent power. Including a representation of the angle between the two waveforms in the form of power factor (see PF) yields the real power.
VendorA vendor is the company, manufacturer or owner of a specific device that can be deployed. For example, Cisco and Juniper manufacture devices that can be launched into the ENE platform. Each vendor may have one or more devices offered on ENE, and the vendor usually has a uniform licensing model and other services for their library of available devices.
VFDVariable Frequency Drive, a device which supplies AC power of varying frequency, typically used to control the speed of induction motors. In the data center, it is common to vary the speed of fans, pumps, and chillers.
Virtual DeviceThe Virtual Device is the software "image" that launches on the ENE platform when a user selects a device. The device could be a router, firewall or other types. This image is generally specific to a vendor (for example: Cisco) and specific device ID that the vendor has integrated with our platform. From this Virtual Device, you can create connections like you would from a port on ECX.
vNFA virtual Network Function (vNF) is similar to the term NFV but typically refers to a discrete task, feature or service that does one thing in a larger solution. For example, a piece of code that can stand as a service that performs IP Address translation might be a vNF.
VNIVirtual Network Interface
WWatt, a unit of power, commonly used in electrical discussion, watts are the product of potential (volts, see V) and current (amps, see A). If the current and voltage are AC, the relationship between watts, volts and amps includes power factor (see PF), watts = volts x amps x PF.
Waterside EconomizerA system which uses a source other than a chiller to cool the secondary loop water used by the AHUs. This typically consists of either a dry cooler or cooling tower, piping, valves and in the case of a cooling tower, it also includes a heat exchanger since the secondary loop water is treated completely differently than the primary loop water and is typically much "better" water.
Water Usage Effectiveness (WUE)A sustainability metric defined by The Green Grid, which is a measure of the water used on-site for data center operations including humidification and on-site evaporation for cooling or energy production. WUE is calculated by dividing “annual water usage” by the “energy consumption of the IT computing equipment”. The units of WUE are liters/kilowatt-hour (L/kWh).
Wet-Bulb TemperatureThe temperature of the air measured using a wet-bulb thermometer, that is, the temperature to which a wet surface can be cooled by evaporation. This temperature is affected by both the dry bulb temperature and the dew point of the air. Dryer air has a lower wet bulb temperature. This is a design constraint when utilizing cooling towers or evaporative pads in the cooling process.
WgInches of water column, a unit of pressure based on the height of a column of water supported by the pressure differential between the top and bottom of the column. 1-inch wg = .036 psi.
WIPWork in Progress
Work CellThe area of a rack and the related area immediately in front of and behind the rack. Standard racks are 2 feet wide and 4 feet deep. Standard aisles are 4 feet wide, so half of that space is workspace for a given rack. This results in a standard work cell of 16 square feet. Actual work cell size varies with data center design.
WPSFWatts per Square Foot, a unit of power density. In a data center this is a bulk term that refers to the total load in a space divided by the total area of that space. This is a design parameter for total capacity of the cooling and power systems and is used in conjunction with point load (the amount of load in a small space such as a rack).
WUESee Water Usage Effectiveness (WUE).
Z-SideNon-Ordering Customer side (often but not always a Carrier).